A GIS ring main unit is 350mm to 600mm wide with no rear clearance needed. A metal enclosed switchgear panel for the same function runs 800mm or wider. In a 10-feeder substation, GIS saves roughly half the floor space. That is often the difference between a viable urban site and no site.
Yes. We build solid insulated switchgear with epoxy-encapsulated conductors and air insulated alternatives. Both meet IEC 62271. Solid insulated is compact like GIS with no gas. Air insulated is the traditional option. The choice depends on your site's environmental regulations and space.
Three-position load break switches for ring switching — closed, open, and earthed. Transformer feeders protected by fuses or vacuum circuit breakers. Fault isolation is automatic: a cable fault opens the switches on either side, and the rest of the ring stays energized. Motorized operation available for remote SCADA switching.
Yes. SF6 has high global warming potential, so we manage it rigorously. Sealed tanks leak under 0.1 percent per year. Gas handling uses recovery equipment, never venting. End-of-life SF6 is recovered and recycled. We provide gas handling documentation and leak rate data. For sites with SF6 restrictions, we offer air insulated and solid insulated alternatives.
Effectively, yes. The SF6 tank is sealed and leak-tested to under 0.1 percent per year. No dust ingress. No oxidation. No atmospheric contamination. Routine maintenance is a visual inspection and a gas pressure check. The tank is not opened for 20-plus years under normal operation.
12kV to 40.5kV. Standard ring main units at 12kV and 24kV. Extended range to 40.5kV for substation incomers. Ring main rating 630A standard, 1250A available. Transformer feeders rated 200A with fuse or breaker protection. All IEC 62271 type-tested.
Gas insulated switchgear uses SF6 inside a sealed tank as the insulating medium. SF6 has three times the dielectric strength of air, so clearances shrink and the whole assembly fits in half the footprint. Air insulated switchgear uses atmospheric air and needs more space. A GIS switchgear panel is 350mm to 600mm wide. An AIS panel needs about 800mm.
Yes. You specify the protection relay — Siemens, ABB, Schneider, SEL. CT and VT ratios per feeder. Differential, directional overcurrent, or distance protection. Busbar differential if required. Modbus or IEC 61850 for SCADA. Our engineering team reviews your protection coordination study and configures each panel accordingly.