PRODUCTS
Home / Products / Circuit Breaker / Vacuum circuit breaker / ZN85-40.5 Handcart Type Vacuum Circuit Breaker

ZN85-40.5 Handcart Type Vacuum Circuit Breaker

The ZN85-40.5 handcart type vacuum circuit breaker stands as a pinnacle of indoor high-voltage switchgear technology, tailored for three-phase AC systems operating at 50Hz and rated at 40.5kV. This pivotal device serves industrial and mining enterprises, power generation facilities, and electrical substations, adeptly managing load currents, overload currents, and fault currents, especially in scenarios demanding frequent operation.
Rated Voltage:
Rated Current:
Availability:
facebook sharing button
twitter sharing button
line sharing button
linkedin sharing button
whatsapp sharing button
sharethis sharing button
  • ZN85-40.5

  • Giantele

  • 40.5kV

  • 1250A,1600A,2000A,2500A

  • 50Hz

  • Three

  • 1pcs

Overview 

The ZN85-40.5 handcart type vacuum circuit breaker stands as a pinnacle of indoor high-voltage switchgear technology, tailored for three-phase AC systems operating at 50Hz and rated at 40.5kV.   This pivotal device serves industrial and mining enterprises, power generation facilities, and electrical substations, adeptly managing load currents, overload currents, and fault currents, especially in scenarios demanding frequent operation.   Its design, manufacturing, and testing processes adhere strictly to the GB/T 11022-1999 standards and other relevant criteria, ensuring unparalleled performance and safety..


Environmental Conditions

  • The upper limit of ambient temperature is +40C, and the average value measured within 24 hours does not exceed 35C;  Lower limit -15℃.

  • The altitude does not exceed 1000m.

  • Relative humidity: the daily average does not exceed 95% The monthly average value does not exceed 90%.

  • Water vapor pressure: daily average does not exceed 2.2kPa, monthly average does not exceed 1.8kPa.

  • The surrounding air is not significantly contaminated by dust, smoke, corrosive or combustible gases, vapors and salt spray.

  • When used under the above normal environment and other conditions specified in GB/T11022-1999, the user can negotiate with the manufacturer to solve the problem.


Product Features

  • Advanced Arc Extinguishing and Power Interruption: Leveraging cutting-edge vacuum arc extinguishing technology, this circuit breaker minimizes arc duration and enhances power interruption capabilities, facilitating stable system operations.

  • Robust Handcart Structure for Enhanced Safety: Its handcart design simplifies installation and maintenance processes, incorporating "five-prevention" safety features to safeguard operators.

  • Exceptional Insulation Quality: The use of premium insulation materials and composite insulated pole columns guarantees consistent insulation performance, even under challenging humidity or extreme conditions.

  • Versatile Operation: Designed for both manual and electric operation modes, it accommodates remote control functionalities to meet the dynamic needs of contemporary electrical grids.

  • Modularity and Compatibility: Its modular design ensures ease of assembly and disassembly.   When paired with various high-voltage switchgear like the KYN61-40.5, it demonstrates remarkable compatibility.

  • Broad Application Spectrum: Beyond its traditional use in industrial, mining, and electrical substations, it's also suitable for any setting that requires reliable power interruption and safety mechanisms.

  • Adaptable to Diverse Environments: Engineered to operate flawlessly in temperatures ranging from -40℃ to +40℃, it is resilient against environmental fluctuations.

  • Cost-Effective with Minimal Maintenance: The device's longevity and reduced maintenance demands translate into substantial savings in operational and maintenance expenses.

Technical Data


NO. Parameter name Unit Numerical value
1 Rated voltage kV 40.5
2 1 min power frequency withstand voltage kV 95
3 Lightning impulse withstand voltage kV 185
4 Rated frequency Hz 50
5 Rated current A 1250,1600,2000,2500
6 Rated short-time withstand current kA 20,25,31.5
7 Rated peak withstand current kA 50,63,80
8 Rated short circuit duration S 4
9 Rated short-circuit breaking current kA 20,25,31.5
10 Rated short-circuit closing current kA 50,63,80
11 Rated operating sequence
0-0.3s- CO -180s- CO
12 Closing time ms 50~100
13 Opening time ms 35~60
14 Loop resistance (without contact arm) μΩ ≤45 (rated current 2500A)
≤60 (rated current 1600A; 2000A)
≤80 (rated current 1250A; 630A)
15 Breaking time ms ≤80
16 Rated short circuit breaking current breaking times Times 20
17 Rated operating voltage V -110/~110,-220/~220
18 Rated working current of switching coil A 1.05/(-110V);0.96/(-220V)
19 Mechanical life time 10000


Schematic diagram of structure