| Rated Current: | |
|---|---|
| Rated Voltage: | |
| Availability: | |
KYN28A-12/24
Giantele
12kV/24kV
50Hz
630A-3150A
IP67
PVOC/SONCAP/ISABS/COC/COI/CRCC/GCC
IEC 62271
Three Phase
1pcs
Overview
AC metal enclosed switchgear of the armored withdrawable type delivers reliable reception, distribution, control, and protection for three-phase AC 50Hz power systems. This medium voltage switchgear adopts an all-metal modular assembly structure with CNC-processed aluminum-zinc steel plates, achieving high precision, strong corrosion resistance, and lightweight construction. Furthermore, its four independently sealed compartments — bus chamber, circuit breaker chamber, cable chamber, and relay instrument chamber — give this metal clad switchgear exceptional safety and operational flexibility.
Operating Conditions
Ambient air temperature: maximum temperature +40℃, minimum temperature -15℃;
Relative humidity: daily average relative humidity: ≤ 95%, daily average water vapor pressure does not exceed 2.2KPa; Monthly average
relative humidity ≤ 90%; The average monthly steam pressure does not exceed 1.8KPa;
Altitude: ≤ 1000m;
Earthquake intensity: not more than 8 magnitude;
The surrounding air should be free from corrosive or flammable gases, water vapor and other obvious pollution;
No severe vibration site;
If it is used under normal conditions beyond GB3906, the user and the Company shall negotiate.
Product Features
Four Independent Sealed Compartments:This metal enclosed switchgear separates the bus, circuit breaker, cable, and relay rooms with individual pressure relief channels for maximum personnel protection.
Withdrawable Handcart Design:The MVSG uses a mid-mounted withdrawable handcart with three positions — disconnect, test, and working — enabling safe operation and easy maintenance without powering down adjacent circuits.
High-Capacity Cable Room:The electrical enclosure cabinet accommodates up to nine single-core cables per bay, providing exceptional flexibility for complex distribution layouts.
Five-Prevention Interlock System:Every power distribution board unit meets full five-prevention mechanical and electrical interlock requirements, eliminating all common human-error operation risks.
Wide Vacuum Circuit Breaker Compatibility:This mv switchgear accepts multiple series of vacuum circuit breakers with 100% interchangeable handcarts across the same specification, simplifying procurement and spare parts management.
Front-Access Installation:This control equipment supports installation, debugging, and maintenance entirely from the front, enabling back-to-back arrangements that significantly reduce substation footprint.
Busbar Arc Fault Containment:Heat-shrink bushing sleeves and insulation end caps on this medium voltage switchgear effectively contain any internal arc fault within the affected cabinet, preventing spread to adjacent units.
| Item | Unit | Data | |
| Rated voltage | kV | 3.6、7.2、12 | |
| Rated frequency | Hz | 50 | |
| Circuit breaker rated current | A | 630、1250、1600、2000、2500、3150 | |
| Rated current of switchgear | A | 630、1250、1600、2000、2500、3150 | |
| Rated short-time withstand current (4S) | kA | 20、25、31.5、40 | |
| Rated peak withstand current (peak) | kA | 50、63、80、100 | |
| Rated short-circuit breaking current | kA | 20、25、31.5、40 | |
| Rated short circuit closing current (peak) | kA | 50、63、80、100 | |
| Rated insulation level 1min power frequency withstand voltage | Between poles, poles to the ground | kV | 24、32、42 |
| Between fractures | kV | 24、32、42 | |
| Lightning impulse Withstand voltage (peak) | Between poles,poles to the ground | kV | 40、60、75 |
| Between fractures | kV | 46、70、85 | |
| Class of protection | The enclosure is IP4X, and the compartment and circuit breaker room doors are IP2X when opened. |
Note: Customizable products (Rated Voltage:24kV), please consult our company for detailed data
.
Mounting size (mm)

| mm | |||||
| Height B | 2300(2200) | ||||
| Width A | Rated current up to 1250A | 800 | |||
| Rated current 1600A and above (altitude 4000m rated current 1250A) | 1000 | ||||
| Depth C | Cable inlet and outlet | 1500 | |||
| Overhead inlet and outlet line | 166 | ||||
| mm | |||||
| Cabinet width A | Cabinet depth B | L1 | L2 | L3 | L4 |
| 800 | 1500 Cable | 530 | 630 | 150 | 490 |
| 1660 Aerial | 530 | 630 | 310 | 650 | |
| 1000 | 1500 Cable | 730 | 830 | 150 | 490 |
| 1660 Aerial | 730 | 830 | 310 | 650 | |
Main circuit scheme diagram