Overview
1.Rating: Rated voltage 400V, 690V, rated current reach to 4000A.
2.Application: mainly applicable in place with high automaticity and need to
communicate with computer, like large power station and petrochemistry system,
as the low voltage distribution device of the distribution and motor controlling,
and reactive power compensation in power system.
3.Level of protection IP30, IP40
4.Standard: IEC60439-1
Working Conditons
1.Ambient air temperature: -15℃~+40℃
Daily average temperature: ≤35℃
When the actual temperature exceed the range, it should be used by reducing thecapacity accordingly.
2.Altitude: ≤2000m
3.Relative humidity: ≤50%, when temperature is +40℃
When temperature is low, larger relative humidity is allowed. when it is +20℃,relative humidity can be 90%. Since the temperature change will make out condensation.
4.Installation inclination: ≤5%
5.Applicable in the places without corrosive and flammable gas.
Note: Customized products are available
Types of meaning
G | C | S | - | ( ) | - | ( ) |
Enclosed switchgear | Withdrawable type | Zhegui electrical system | Main circuit scheme No. | Auxiliary circuit scheme No. |
High quality shell material
Aluminium zinc plate, surface processing of epoxy resin, beautiful and durable
Intelligent controller
Intelligence wisdom, science and technology make electricity safer
Professional customization
The interior is carefully designed
At the bottom of the drawer
Drawer bottom plug type design, convenient wiring installation.
PRODUCT SIZE DESCRIPTI
Main technical parameters
Rated voltage of main circuit(V) | AC380(400)、(660) | |
Rated voltage of auxiliary circuit (V) | AC220、380(400)DC110、220 | |
Rated frequency (Hz) | 50(60) | |
Rated insulation voltage (V) | 660(1000) | |
Rated current (A) | horizontal bus | W4000 |
Vertical busbar (MCC) | 1000 | |
Rated short-time tolerable current of bus (kA/1 s) | 50, 80 | |
Rated peak tolerance current of bus (kA/ 0.1s) | 105, 176 | |
Power frequency test voltage (V/1min) | main circuit | 2500 |
ancillary circuit | 1760 | |
generatrix | three-phase four-wire system | A. B、C、PEN |
Three phase five wire system | A. B、C、PE、N | |
level of protection | IP30、 IP40 |